Component Function Check
1.CHECK REFRIGERANT PRESSURE SENSOR OVERALL FUNCTION
Is the inspection result normal? YES >> INSPECTION END
NO >> Proceed to EC-465, "Diagnosis Procedure".
Diagnosis Procedure
1.CHECK REFRIGERANT PRESSURE SENSOR POWER SUPPLY

Is the inspection result normal? YES >> GO TO 3.
NO >> GO TO 2.
2.CHECK REFRIGERANT PRESSURE SENSOR POWER SUPPLY CIRCUIT
Is the inspection result normal? YES >> Perform the trouble diagnosis for power supply circuit.
NO >> Repair or replace error-detected parts.
3.CHECK REFRIGERANT PRESSURE SENSOR GROUND
Is the inspection result normal? YES >> GO TO 4.
NO >> Repair or replace error-detected parts.
4.CHECK REFRIGERANT PRESSURE SENSOR INPUT SIGNAL CIRCUIT
Is the inspection result normal? YES >> GO TO 5.
NO >> Repair or replace error-detected parts.
5.CHECK INTERMITTENT INCIDENT
Check intermittent incident. Refer to GI-39, "Intermittent Incident".
Is the inspection result normal? YES >> Replace refrigerant pressure sensor. Refer to HAC-110, "Removal and Installation" (For automatic air condittioner), or HAC-191, "Removal and Installation" (For manual air condittioner).
NO >> Repair or replace error-detected parts.
Cooling fan
Malfunction indicator lampWiring diagram
Manual air conditioning system
Wiring Diagram
Manual heater system
Wiring Diagram
...
Abs branch line circuit
Diagnosis procedure
1.Check connector
Turn the ignition switch OFF.
Disconnect the battery cable from the negative terminal.
Check the terminals and connectors of the abs actuator and electric unit
(control unit) for damage, bend
and loose connection (unit side and connector side).
...
Diagnosis system (ECM)
Diagnosis description : 1st trip detection
logic and two trip detection logic
When a malfunction is detected for the first time, 1st trip DTC and 1st trip
Freeze Frame data are stored in the
ECM memory. The MIL will not illuminate at this stage. <1st trip>
If the same malfunction is dete ...